Orifice Flanges

The orifice flange union is composed of two orifice flanges, an orifice plate, bolts, nuts, jack screws, and two gaskets.

From: The Engineer's Guide to Plant Layout and Piping Design for the Oil and Gas Industries, 2018

Add to Mendeley

Heat Exchangers

Seán Moran, in Process Plant Layout (Second Edition), 2017

23.13 Instrumentation

Orifice flanges in exchanger piping are usually in horizontal piperuns just above headroom level, but they may be placed at a lower level for convenience in attaching manometers and inserting orifice plates. Locally mounted pressure and temperature indicators on equipment or process lines, sight glasses, and level controllers should be visible from access aisles; and valves should be accessible from the aisles.

Where practicable, it is recommended that sufficient instrumentation is provided to be able to obtain a robust heat balance across the exchanger, thereby allowing its performance to be monitored in operation and facilitating straightforward analysis and troubleshooting.

It may be sufficient to simply make provision for the later use of temporary instrumentation. The designer should therefore always consider the addition of thermowells on heat exchanger inlet and outlet connections to allow performance monitoring.

Instruments shall be within the boundary of the isolating valves on either side of the heat exchanger such that when the heat exchanger is isolated by closing the valves for maintenance, the instruments shall also be isolated.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128033555000238

Engineering Aspects for Plant Piping Systems

Alireza Bahadori PhD, CEng, MIChemE, CPEng, MIEAust, RPEQ, in Oil and Gas Pipelines and Piping Systems, 2017

13.2.6.4 Flow Measurement

1.

Orifice flange connections should be in accordance with standards.

2.

For inline flow measurement devices, the manufacturer’s installation requirements should be followed.

3.

Piping and primary valving at the orifice fitting or other flow measurement device should conform to the line specification.

4.

Line-tap connections should conform to the requirements for pressure tapping.

5.

Orifice flanges should be installed in horizontal pipes, as far as possible. When it is impossible to find a sufficient meter run in a horizontal piping, orifices may be installed in a vertical piping with upwards flow for liquids and downward flow for gas and steam.

6.

The minimum meter run required for both upstream and downstream of the orifice flanges should be in accordance with standards.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128037775000137

Flange Basics

Roy A. Parisher, Robert A. Rhea, in Pipe Drafting and Design (Fourth Edition), 2022

Orifice Flange

Of the flanges discussed, the orifice flange is the only one that actually performs a function. The function of the orifice flange is to measure the rate of the flow of the commodity through the piping system. Orifice flanges are easy to recognize because they have a hole drilled through the face of the flange perpendicular to the pipe. They also have an additional set of bolts called jack screws. These screws are used to help separate the flanges so inspection and/or replacement of the orifice plate can be performed. The orifice flange is a single component of the orifice flange union assembly (Figure 4.26). The orifice flange union is composed of two orifice flanges, an orifice plate, bolts, nuts, jack screws, and two gaskets. A representation of an unbolted and separated orifice flange union assembly is depicted in Figure 4.27.

Figure 4.26. Orifice flange.

Figure 4.27. Unbolted orifice flange union assembly.

The orifice flange union is used to measure, or meter, the amount of pressure drop through the orifice plate. The length of pipe within the piping system where orifice flanges are installed and where these measurements are recorded is known as a meter run. Figure 4.28 shows the orifice flange union assembly installed in a meter run. The broken-out section shown in Figure 4.29 shows the internal view of a meter run.

Figure 4.28. Orifice flange union assembly.

Courtesy of Nisseki Chemical Texas Inc., Bayport, Texas.

Figure 4.29. Broken-out section of meter run.

The orifice plate, which is not typically furnished with the orifice union assembly package, looks similar to a large ring washer with a handle attached. When fully assembled, the orifice plate is sandwiched between the orifice flanges. Valve taps are inserted into pressure holes that allow for the attachment of field monitoring equipment so accurate measurements can be recorded.

Orifice flanges can be either weld neck, slip-on, or threaded. The weld neck and threaded orifice flanges are manufactured in 300# and larger pound ratings. However, the slip-on orifice flange is only available as a 300# raised face flange. The single-line and double-line drawing symbols for the orifice flange are shown in Figure 4.30.

Figure 4.30. Orifice flange drawing symbols.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128220474000054

Piping

Ian SuttonAuthor, in Plant Design and Operations (Second Edition), 2017

Flanges

Pipe flanges are used to connect pipe sections to other pipe sections and equipment. (Flangeless valves are described in Chapter 5: Valves.) Their use means that pipe can be assembled and disassembled with the need for cutting or welding. However, by providing a breakable joint in the piping they create a potential leak source.

Fig. 4.4 shows two sections of pipe with a flange on each. They are bolted together with a gasket between them.

Figure 4.4. Pipe flanges.

Many different standards for flange design are in use. They include ASA/ANSI/ASME (USA), PN/DIN (European), BS10 (British/Australian), and JIS/KS (Japanese/Korean). In most cases these different standards are not mutually compatible. Moreover the different pressure rating for flanges within a class are not generally interchangeable. For example, ANSI/ASME 150 and ANSI/ASME 300 are not compatible.

The ASME standards include:

B16.1―Cast Iron Flanges and Flanged Fittings

B16.5―Pipe Flanges and Flange Fittings (NPS 1/2 through 24)

B16.24―Cast Copper Alloy Pipe Flanges and Flanged Fittings

B16.36―Orifice Flanges

B16.42―Ductile Iron Pipe Flanges and Pipe Fittings (NPS 26 through 60)

B16.47―Large Diameter Steel Flanges (NPS 26 through 60)

The ASME standards divided flanges into different classes. B16.5 provides the working pressure limit of a flange depending on the material category, temperature, and classification. The material categories are as follows:

Carbon and low alloy steels

Austenitic stainless steels

Nickel alloys.

Table 4.5 is an example of an ASME flange rating specification.

Table 4.5. Flange Rating Table

Nominal Designation Forgings Castings Plates
C–Si A 105a A 216 Gr. WCBa A 515 Gr. 70a
C–Mn–Si A 350 Gr. LF2a A 516 Gr. 70a,b
C–Mn–Si–V A 350 Gr. LF6 Cl.c
3½ Ni A 350 Gr. LF3 A 537 Cl. 1d
Working Pressure by Classes (bar)
Class Temperature (°C) 150 300 400 600 900 1500 2500
–29 to 38 19.6 51.1 68.1 102.1 153.2 255.3 425.5
50 19.2 50.1 66.8 100.2 150.4 250.6 417.7
100 17.7 46.6 62.1 93.2 139.8 233.0 388.3
150 15.8 45.1 60.1 90.2 135.2 225.4 375.6
200 13.8 43.8 58.4 87.6 131.4 219.0 365.0
250 12.1 41.9 55.9 83.9 125.8 209.7 349.5
300 10.2 39.8 53.1 79.6 119.5 199.1 331.8
325 9.3 38.7 51.6 77.4 116.1 193.6 322.6
350 8.4 37.6 50.1 75.1 112.7 187.8 313.0
375 7.4 36.4 48.5 72.7 109.1 181.8 303.1
400 6.5 34.7 46.3 69.4 104.2 173.6 289.3
425 5.5 28.8 38.4 57.5 86.3 143.8 239.7
450 4.6 23.0 30.7 46.0 69.0 115.0 191.7
475 3.7 17.4 23.2 34.9 52.3 87.2 145.3
500 2.8 11.8 15.7 23.5 35.3 58.8 97.9
538 1.4 5.9 7.9 11.8 17.7 29.5 49.2
a
Upon prolonged exposure to temperatures above 425°C, the carbide phase of steel may be converted to graphite. Permissible but not recommended for prolonged use above 425°C.
b
Not to be used over 455°C.
c
Not to be used over 260°C.
d
Not to be used over 370°C.

So, for example, if the piping being designed is fabricated from one of the metals shown, has a temperature of 200°C and a working pressure of 50 bar then Class 400 will be selected.

The flange faces are also made to standardized dimensions and are typically flat face, raised face, tongue and groove, slip on or ring joint types (Huitt, 2007). The standard will also usually specify gasket and bolt requirements. The flange standards sometimes refer to the pressure vessel and piping codes already discussed.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128128831000048

Piping Systems

Roy A. Parisher, Robert A. Rhea, in Pipe Drafting and Design (Third Edition), 2012

Meter Runs

Developing a piping system that incorporates smooth and consistent flow characteristics is imperative in any piping facility. The ability to measure the rate of flow of a commodity is necessary at various stages throughout a facility. Rate of flow is simply a measurement of the amount of commodity flowing through a pipe in a specified amount of time. The most common way to achieve this is through a section of pipe referred to as a meter run. A meter run is the name given to a straight run of pipe that uses a set of orifice flanges to measure the rate of flow.

Recall from the discussion in Chapter 4, orifice flanges have valve taps that allow monitoring equipment to be attached, which records the differential pressure of a commodity traveling through an orifice plate (see Figure 12.9).

Figure 12.9. Orifice flanges with instrumentation.

Courtesy of Nisseki Chemical Texas, Inc., Bayport, Texas.

The critical part of a meter run is the orifice plate. The orifice plate is a ⅛″ thick, flat, circular disk, made of metal, having a flat handle (see Figure 12.10). The orifice plate, with a gasket on either side, is sandwiched between two orifice flanges. An exploded view of an installed orifice plate is shown in Figure 12.11. As you can see, a hole is machined through the center of the plate to allow commodity to pass through. This hole is approximately 75% of the diameter of the pipe. The size of the hole in the orifice plate, relative to the size of the pipe, is known as the beta factor. Depending on the application, numerous beta factors can be used. However, 0.75 is the one most commonly used in meter run calculations. By attaching monitoring equipment to the valve taps, the rate of flow of the commodity can be measured as flow travels along the pipe and through the orifice plate.

Figure 12.10. Orifice plate.

Figure 12.11. Installed orifice plate.

To receive the most accurate reading possible, turbulence within the pipe must be kept to a minimum. Flow turbulence is created by obstructions in the configuration from items such as fittings and valves. A smooth, consistent flow is created by providing a sufficient amount of straight pipe before and after the orifice flanges. Therefore, the length of the run of pipe before, or upstream of, the orifice plate and the length of the section of pipe after, or downstream of, the plate is precisely calculated. These upstream and downstream measurements are established by using precise lengths of pipe that are based on the diameter of the pipe being used. Additional factors also affect how these lengths are calculated. For example, a different beta factor can be used or a multiplane pipe configuration before the orifice plate may be required. However, a general rule-of-thumb formula of 30 pipe diameters upstream and 6 pipe diameters downstream provides adequate distance to create smooth flow in the meter run. A graphical representation of the values used to calculate these lengths is shown in Figure 12.12.

Figure 12.12. Meter run pipe lengths.

To calculate the lengths shown in Figure 12.12, simply multiply the upstream and downstream diameters times the nominal pipe size. The following is an example to calculate the upstream and downstream pipe lengths for a meter run installed in a 6″ pipe configuration.

Upstreamdistance=30(diameters)×6=180=15-0
Downstreamdistance=6(diameters)×6=36=3-0

Again, the formula above is a rule-of-thumb guide. Specific values for upstream and downstream diameters vary depending upon the configuration of the piping system in which the orifice flanges are installed. Review the client’s specifications for the project you are working on to verify the correct upstream and downstream diameters.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780123847003000128

Piping Systems

Roy A. Parisher, Robert A. Rhea, in Pipe Drafting and Design (Fourth Edition), 2022

Meter Runs

Developing a piping system that incorporates smooth and consistent flow characteristics is imperative in any piping facility. The ability to measure the rate of flow of a commodity is necessary at various stages throughout a facility. Rate of flow is simply a measurement of the amount of commodity flowing through a pipe in a specified amount of time. Sometimes commodities are flowing too quickly through the piping system and must be constrained and/or controlled. The reduction of head pressure is a required drop in pressure and must be monitored continuously. The most common way to achieve this is through a section of pipe referred to as a meter run. A meter run is the name given to a straight run of pipe that uses an orifice flange union assembly, a set of orifice flanges and restriction plate, to measure the rate of flow and drop in pressure.

Recall from the discussion in Chapter 4, Flange Basics, orifice flanges have valve taps that allow monitoring equipment to be attached which records the differential pressure of a commodity traveling through an orifice plate. Figure 12.10 is a photograph of the instrumentation attached to an orifice flange union assembly.

Figure 12.10. Orifice flanges with instrumentation.

Courtesy of Nisseki Chemical Texas, Inc., Bayport, Texas.

A critical component in a meter run is the orifice plate. Most often, the orifice plate is a thin, flat, circular disc, made of metal, having a flat handle. Depending on the methods being used and the data being gathered, different orifice plates types are installed. Figure 12.11 provides examples of various orifice plate configurations. Although they are single-stage orifices, some restriction plates have multiple openings in the plate. Multihole plates are installed when commodity flow rates are extremely high. High flow rates create a loud, high-pitched noise as the commodity flows through a restriction plate. Multiple holes divide the incoming commodity into several smaller flow streams, thus reducing the noise. The cumulative area size of all of the hole openings establish the amount of pressure drop downstream of the restriction orifice.

Figure 12.11. Orifice plate styles.

The orifice plate, with a gasket on either side, is sandwiched between two orifice flanges. An exploded view of an installed orifice plate is shown in Figure 12.12. In this example, a single hole is machined through the center of the plate to allow commodity to pass through. The size of the hole in the orifice plate, relative to the size of the pipe, is known as the Beta (β) Ratio or Beta (β) Factor. Depending on the application, numerous Beta (β) Ratios can be used. By attaching monitoring equipment to the valve taps, the rate of flow of the commodity and its drop in pressure can be measured as flow travels along the pipe and through the orifice plate.

Figure 12.12. Installed orifice plate.

To receive the most accurate reading possible, turbulence within the pipe must be kept to a minimum. Flow turbulence is created by obstructions in the configuration from items such as fittings and valves. A smooth, consistent flow is created by providing a sufficient amount of straight pipe before and after the orifice flanges. Therefore the length of the run of pipe before, or upstream, of the orifice plate and the length of the section of pipe after, or downstream, of the plate is precisely calculated. These upstream and downstream measurements are established by using precise lengths of pipe which are based on the diameter of the pipe being used. Additional fitting and valve installations will affect how these lengths are calculated. For example, a different Beta (β) Ratio, ranging from 0.30 to 0.75 (30%–75%), can be used or a multiplane pipe configuration before the orifice plate may be required. As a general rule-of-thumb, 30 pipe diameters upstream and six (6) pipe diameters downstream will provide adequate lengths of pipe to create smooth flow in the meter run. A graphical representation of the values used to calculate these lengths is shown in Figure 12.13.

Figure 12.13. Meter run pipe lengths.

To use the values shown in Figure 12.13, simply multiply the upstream and downstream diameters times the nominal pipe size. The following is an example to calculate the upstream and downstream pipe lengths for a meter run installed in a 6″ pipe configuration.

Upstreamdistance=30(diameters)×6=180=15-0
Downstreamdistance=6(diameters)×6=36=3-0

Again, the formula above is a rule-of-thumb guide. Specific values for upstream and downstream diameters vary depending upon the configuration of the piping system in which the orifice flanges are installed. Space limitations, configuration components, and routing orientation such as those shown in Figure 12.14 dictate upstream and downstream pipe lengths for prescribed Beta (β) Ratios. One of the more commonly used Beta (β) Ratios in meter run calculations is 0.75. This means the area of the hole or holes machined in the orifice plate are approximately 75% of the inside diameter of the pipe. Figure 12.14 represents the minimum upstream and downstream pipe lengths when a Beta (β) Ratio of 0.75 is used. Review specific project specifications to verify the correct upstream and downstream diameters.

Figure 12.14. 0.75 Beta (β) Ratio meter run pipe lengths.

Occasionally, more than a single orifice plate is required. Multistage orifice assemblies, illustrated in Figure 12.15, have multiple phases through which the commodity must flow in order to achieve the desired result. Like single-plate orifices, multistage restriction orifices have instrumentation connections on both ends to accurately read specific characteristics of the commodity as it exits the assembly.

Figure 12.15. Multistage orifice.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128220474000108

Instrumentation

Seán Moran, in Process Plant Layout (Second Edition), 2017

36.10 Maintenance

36.10.1 Flowmeters

While the installation of venturi tubes requires no special consideration, pitot tubes require removal clearance and accessibility. Access is needed to all flow detectors but clearance for cover removal should also be allowed for the inspection and adjustment of differential-pressure cells associated with the flow detectors.

Care must be taken to ensure ample clearance around orifice plates and tappings for cleaning and rodding out. A minimum clearance of 600 mm is required between walls and orifice flanges.

Complex analytical instruments such as particle size analyzers and TOC meters should be accessible for in situ maintenance from a floor. For complete removal of instruments weighing more than 9 kg, a hitching point or davit should be considered unless near the floor, in which case access should be left for a truck to be wheeled underneath.

Some instruments may have to be enclosed (sometimes under slight positive pressure) in their own local environment and room must be left for such enclosures. This may be either for protection of the instruments themselves or because the instrumentation may contain ignition sources.

Instrument mechanisms are often delicate and instruments should not be located where they can be damaged by the removal of other items during maintenance. They should also not be installed near vibrating machinery and usually require electrical screening.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128033555000366

Pump Best Practices

W.E. Forsthoffer, in Forsthoffer's Best Practice Handbook for Rotating Machinery, 2011

The affinity laws

In actual practice, the affinity laws provide an approximation between flow, head and horsepower as pump impeller diameter or speed is varied. The values actually observed will vary somewhat less than predicted by the affinity laws. That is, the actual exponents in the affinity equations are slightly less than their stated values and are different for each pump. This results from friction in hydraulic passages and impellers, leakage losses and variation of impeller discharge vane angles when diameters are changed. Pump manufacturers should be contacted to confirm actual impeller diameters and speed changes to meet new duty requirements.

Best Practice 2.10

Install discharge flange orifices for centrifugal pumps with less than 5% head rise to ensure stable pump operation.

Centrifugal pumps with flat head vs. flow curves (less than 5% head rise from rated to zero flow) produce rapid flow changes for small process changes.

Size the impeller for increased head (to compensate for the orifice pressure drop).

Installing a discharge orifice in the pump volute or on the discharge flange will produce the desired head rise, and will result in a pump characteristic that produces gradual flow changes for small process changes.

This procedure is especially effective for high speed pumps which have a characteristic flat, low head rise performance curve.

Lessons Learned

Failure to correct pumps, especially high speed type (integral gear centrifugal), with discharge orifices, to produce a performance curve characteristic of sufficient head rise will lead to low pump MTBF.

Low head rise curves, less than 5%, have resulted in the following reliability issues:

Rapid inducer and/or impeller wear

Pump seizure

Bearing failure

Seal failure

Shaft breakage

Gear box failure

Benchmarks

This best practice has been used since the mid-1970s in all high speed pump applications, and where any centrifugal pump had a low head rise characteristic. This has resulted in centrifugal pump operation of optimum safety and reliability. MTBFs using this best practice have been greater than 80 months.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780080966762100025

Codes, recommendations, and sizing methods

Marc Hellemans, in Overpressure Protection in the Process Industry, 2022

6.2 US directives

Here is an overview of the applicable codes which might relate to overpressure protection:

AISI: American Iron and Steel Institute.

ANSI: American National Standards Institute.

ASME: American Society of Mechanical Engineers: Boiler and Pressure Vessel Code: compilation of rules and guidance covering numerous types of construction.

Chapter I—Power boilers and direct fired pressure vessels.

Chapter II—Materials.

SA 216—Carbon-steel castings suitable for fusion welding for high0000 temperature service.

A 217—Martensitic stainless steel and alloy steel castings for pressure containing parts suitable for high-temperature service.

SA 351—Austenitic steel castings for pressure containing parts.

SA 494—Nickel and nickel alloy castings.

Chapter III—Nuclear.

Chapter IV—Heating boilers.

Chapter VII—Care of power boilers.

Chapter VIII—Rules for construction of unfired pressure vessels and overpressure protection devices.

Chapter IX—Welding and brazing qualification.

Chapter XII—Transportation tanks.

ASME Standards:

B978-0-323-90956-3.25—Butt welding Ends.

B978-0-323-90956-3.34—Valves—Flanged, threaded and welding ends.

B978-0-323-90956-3.36—Orifice Flanges.

B978-0-323-90956-3.5—Pipe flanges and flanged fittings.

B978-0-323-90956-3.1—Power piping.

B978-0-323-90956-3.3—Process piping.

B978-0-323-90956-3.4—Pipeline transportation systems for liquid hydrocarbons and other liquids.

B978-0-323-90956-3.8—Gas transmission and distribution systems.

PTC 25—Pressure Relief Devices.

API: American Petroleum Institute.

API Standard 520—Sizing, selection and installation of pressure-relieving devices in refineries.

Part I—Sizing and selection.

Part II—Installation.

API Standard 521—Guide for pressure-relieving and depressuring Systems.

API Standard 526—Flanged Steel Pressure Relief Valves.

API Standard 527—Testing and acceptance for set pressure and seat tightness of pressure relief valves.

API Recommended Practice 576—Inspection of pressure relieving devices.

API Standard 2000—Venting atmospheric and low-Pressure Storage Tanks.

ASTM: American Society for testing and materials.

NB: National Board (of Boiler and Pressure Vessel Inspectors).

MSS: Manufacturers Standardization Society (of the valves and fittings industry).

SP-25: Standard marking systems for valves, Fittings, Flanges and Unions (not applicable to pressure safety valves—refer to ASME B&PVC, Chapter VIII, UG129).

SP-44—Steel Pipeline Flanges.

SP-55—Quality Standard for Steel Castings for Valves, Flanges, Fittings, and Other Piping Components—Visual Method for Evaluation of Surface Irregularities.

SP-61—Pressure Testing of Steel Valves (not applicable to pressure safety valves—refer to API STD 527).

The primary codes relating to pressure relief devices are ASME I, III, and VIII. What is not covered by ASME:

Vessels with pressures below 1,03 Barg.

Pipelines outside process installations.

Water supply & water discharge network (utilities outside the process).

Vessels protected by “system design.”

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780323909563000046

Pilot plant and industrial-scale operations for biodiesel production

V. Vishal Malolan, ... A. Arumugam, in Production of Biodiesel from Non-Edible Sources, 2022

6.3.7.2 Hydrodynamic cavitation reactors

HC is one of the recent technologies and for biodiesel production at an industrial scale due to the comprehensible level of its scale-up. It is used as a process enhancer, resulting in a significant increase in energy consumption, yields, and reaction time (Sun et al., 2020). These enhancements may be particularly useful in the next generation of biodiesel plants, especially to the looming and recent global scenario of low petroleum prices, in which the biodiesel industry is struggling to remain competitive and financially viable. A pump, control valves, orifice plate, and flanges are typically utilized in all HC reactors used for biodiesel processing, which is schematically described in Fig. 6.8. The storage tank is encompassed by a cooling jacket, and the pressure is maintained by a regulated cooling water system. The storage tank is encompassed by a cooling jacket, and the pressure is maintained by a regulated cooling water system. Tweaking in the flow field in high-speed/high-pressure devices, as well as the passage of the liquid via a constriction such as an orifice pad, venturi, or throttling valve, may potentially trigger HC. Due to turbulence caused by liquid circulation currents, HC causes the creation of local hotspots, the release of highly reactive free radicals, and augmented mass transfer rates. In collation to traditional ultrasound-based reactors, these caveats can be used to intensify a variety of bioprocessing applications in an energy-efficient manner. Furthermore, it is a less exorbitant solution that uses around half as much energy as the traditional mechanical stirring process. HC could produce cavitating conditions similar to acoustic cavitation, with a prolific effect on mixing immiscible liquids. Despite having been probed on and developed for nearly 30 years, HC technology is yet to be widely utilized in industrial applications around the world. The majority of current research focuses on applications; however, the features of HCRs have received attention, which has a significant impact on the growth and implementation of HC technology (Moholkar et al., 1999).

Figure 6.8. Hydrodynamic cavitation reactor system for the biodiesel production (Sun et al., 2020).

From Sun, X., Chen, S., Liu, J., Zhao, S., & Yoon, J. Y. (2020). Hydrodynamic cavitation: A promising technology for industrial-scale synthesis of nanomaterials. Frontiers in Chemistry, 8. https://doi.org/10.3389/fchem.2020.00259.

Asif et al. (2017) performed the chemical interesterification anatomization for rubber seed (Hevea brasiliensis) oil using four separate designed orifice devices in a pilot model HC framework. The optimal cavitation system was defined as the orifice plate with a 1 mm diameter of 21 holes and a 3 bar upstream pressure. The ideal RSM conditions were 14:1 of molar ratio in the existence of a 0.75 wt.% catalyst at 50°C for a 20 min reaction cycle. A juxtaposition for the study of HC and mechanical stirring portrays that the reaction rate and yield efficiency of HC were 3.4-fold shorter and 3 times greater than mechanical stirring. The rest of the fuel characteristics concurred with the requirements of EN 14214 and ASTM D6751 (Asif et al., 2017).

A sub-type of HC reactors that uses a rotor with death-end cavitations is called shockwave power reactors (SPRs). SPRs are in fact rotating hydrodynamic reactors that have a rotor with dead-end cavities. A spinning rotor generates centrifugal force, which creates low-pressure zones at regions of the cavities which are in proximity to the rotor axis. This allows the formation of micro-cavities when the reactant mixtures are passed in through the rotor. As with cavitation reactors, the collapse of low-pressure zones collapses the micro-cavities, creating shock waves. However, the cavitation is more harnessed and does not damage the metal surfaces of the rotor. Low-pressure zones are created at the bottom of the cavities due to rotor spinning. An important parameter for these types of reactors in biodiesel production is the rotor to stator ratio (Abbaszadeh-Mayvan et al., 2018). Commercial SPR models from Hydro Dynamics, Inc. promise an annual input capacity of 3–567 Million Gallons of biodiesel from offscouring oils, such as beef tallow, soybean oil, and poultry fat in intermittent operation.

Read full chapter
URL: https://www.sciencedirect.com/science/article/pii/B9780128242957000073